Overview of GRP Water Tank Design Standards

Purpose and Benefits
AQUOSYS's GRP water tanks are engineered to meet essential requirements such as
- Long lifespan
- Hygienic storage conditions
- Leak-proof construction
- Structural stability
- Ease of assembly
The use of standardized panels and bolt assembly allows for customizable tank capacities tailored to various building sizes and structures.
Design Specifications:
Height Range: 1.0 to 5.0 meters
Capacity: 1 to 20,000 tons (cubic meters)
Shapes Available: Square, L-shaped (ㄱ), Inverted L-shaped (ㄴ), Square with central partition (ㅁ), among others
Performance Standards:
Hydrostatic Pressure: Withstands water pressure up to 4 times the standard
Deformation Rate: Less than 1% when filled to capacity
Wind Resistance: Up to 60 m/sec
Seismic Resistance: Horizontal intensity kh = 1/3G
Snow Load Capacity: 200 kg/m², suitable for snowfall up to 1 meter
Illumination Rate: Less than 1%
Fitting Strength: No leakage under a vertical load of 100 kg after installing a 100A fitting
Water Temperature Range: Usable up to 30°C; maximum limit up to 60°C
These specifications ensure that AQUOSYS’s GRP water tanks are suitable for storing clean drinking water while adhering to safety and durability standards.